A compact dual-channel AC current/voltage transmitter with true RMS measurement and three-way isolation for reliable PLC/DCS integration.
| Input Signal: | |
|---|---|
| Output Signal: | |
| Power Supply: | Please select |
| SKU: | |
| Availability: | |
| Quantity: | |
QD89UI AC Current and Voltage Transmitter
QD89UI is a combined current and voltage transmitter designed around “Current & Voltage Measurement in One Module.” Independent current and voltage measurement channels allow two electrical variables to be acquired within one compact device. This integrated structure helps reduce the number of separate measurement modules required in power monitoring and industrial control applications.
QD89UI provides independent output channels for current and voltage measurements. Standard 4–20mA outputs allow both measured variables to be transmitted separately to downstream monitoring and control equipment, while 0–5V and 0–10V voltage outputs are available as options. This makes the transmitter easier to integrate with PLC, DCS and industrial data acquisition systems.
QD89UI uses three-way galvanic isolation between the AC input circuit, DC output circuit and auxiliary power supply. A 2500V AC withstand level provides additional electrical separation between field measurement and downstream control circuits, helping reduce the influence of common-mode interference and ground potential differences.
Working Principle Diagram
Measuring Principle:True RMS (TRMS) sampling; maintains rated accuracy for sinusoidal and non-sinusoidal distorted waveforms
System Accuracy Class:±0.2% F.S., full temperature compensated across operating range
Linearity Error:≤±0.1% F.S.
Temperature Drift Coefficient:≤50ppm/℃; stable readings under wide ambient temperature fluctuations
Step Response Time:≤300ms (10% → 90% rated input)
Frequency Adaptability:45 ~ 65Hz; fully compatible with global 50Hz and 60Hz power systems
Channel Crosstalk:≤-60dB; fully independent current and voltage measuring channels, zero mutual interference
Overload Capacity:Current channel: 2× rated continuous, 10× rated for 10s Voltage channel: 1.5× rated continuous, 2× rated for 10s
Self-Diagnostic Function:Input over-range detection, open-circuit monitoring and internal hardware fault alarm
Dimension Chart
Wiring Diagram