+86-19715617532      sales008@qd-zdk.com
English

PRODUCTS

You are here: Home » Products » Level Measurement » Non-Contact Level Sensor » QDY-SF RF Admittance Level Switch for Sticky Materials

loading

Share to:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

QDY-SF RF Admittance Level Switch for Sticky Materials

The QDY-SF RF Admittance Level Switch provides reliable point-level detection in liquids, sludge, powders, and solids by actively compensating for material buildup and offering adjustable sensitivity and response time.
Power:
Please select
Relay:
Please select
Connected Thread:
Please select
SKU:
Availability:
Quantity:

QDY-SF RF Admittance Level Switch

RF admittance level switch with active buildup compensation for sticky material on sensing probe

Detect the Material, Not the Buildup

QDY-SF uses RF admittance technology with a three-electrode guard-ring design to distinguish actual material contact from buildup on the sensing probe. Active compensation helps prevent false switching caused by viscous coatings, sticky sludge and accumulated dust, reducing unnecessary maintenance in demanding level applications.

adjustable RF admittance level switch for viscous liquids powders and granular solids

Reliable Detection Across Diverse Materials

With continuously adjustable sensitivity from 0.5pF to 100pF, QDY-SF adapts to materials with different dielectric characteristics, including viscous liquids, sludge, powders and granular solids. This makes the same sensing principle suitable for a broad range of point-level detection applications.

RF admittance level switch with high temperature and PTFE corrosion resistant options

Adapt to Demanding Process Conditions

QDY-SF is available in configurations for different process conditions, including standard, high-temperature and corrosion-resistant applications. High-temperature versions support process media up to 250°C continuously, while PTFE wetted options are available for strong acids, alkalis and other corrosive media.

Working Principle Diagram

QDY-SF RF Admittance Level Switch Working Principle Diagram

Technical Specifications

Sensing Principle:RF admittance technology with 3-electrode guard ring design; actively compensates for material buildup on the probe rod


Buildup Compensation Performance:Full active hang-up compensation; no false triggering from viscous coating


Sensitivity Adjustment Range:0.5pF ~ 100pF continuously adjustable; adapts to low-density powders, viscous liquids and granular solids


Switching Point Repeatability:≤±1mm under stable medium conditions


Response Time:0.2s ~ 10s software adjustable; balances fast response and anti-interference stability


False Alarm Suppression:Built-in multi-stage filtering algorithm; eliminates false triggers from material splash


Coating Drift Tolerance:≤0.1pF drift with 2mm sticky material coating; no recalibration required for normal process buildup


Temperature Drift Coefficient:≤0.02pF/℃; stable switching threshold across the full operating temperature span


Self-Diagnosis Function:Real-time fault detection for probe short-circuit, open-circuit, circuit failure and power anomaly


Output Logic Mode:Freely configurable NO / NC relay logic; reverse output without hardware modification

Dimension Chart

image.png

微信图片_20260928101913_515_10.jpg
微信图片_20260928101917_516_10.jpg
Previous: 
Next: 
Tel: +86-400-127-7889 / +86-561-3033839
Phone: +86-19715617532
Add: Building 14, University Science and Technology Park, Fenghuangshan Economic Development Zone, Xiangshan District, Huaibei City, Anhui Province

QUICK LINKS

PRODUCT CATEGORY

MORE LINKS