| Input Signal: | |
|---|---|
| Output Signal : | Please select |
| Channel: | Please select |
| Power Supply: | Please select |
| SKU: | |
| Availability: | |
| Quantity: | |
Multi-Channel Remote I/O Data Acquisition Module
The modular remote I/O platform provides dedicated configurations for multi-channel analog, temperature and digital signal acquisition. Analog models support 8 or 16 channels, temperature models provide 8-channel RTD/thermocouple acquisition, and digital I/O versions combine 8 digital inputs with 8 relay outputs.
Standard Modbus RTU communication over RS485 simplifies integration with industrial control and monitoring systems. Configurable baud rates from 1200 to 115200bps and transmission distances up to 1200m support distributed field data acquisition across larger installations.
Three-way galvanic isolation separates the power supply, field input and RS485 communication circuits. Combined with 1500V AC dielectric isolation, ≥120dB common-mode rejection and industrial EMC protection, the module is designed for reliable signal acquisition in electrically demanding environments.
Technical Specifications | ||||
Parameter | Analog Input Module | Temperature Input Module (RTD/TC) | Digital I/O Module | 3-Port RS485 Hub Module |
Channel Configuration | 8 / 16-channel universal analog input; software configurable per channel | 8-channel universal temperature input; RTD & thermocouple mixed supported | 8 digital inputs + 8 relay outputs | 3 independent RS485 ports + 1 uplink port |
Supported Signal Types | 4-20mA, 0-10mA, 0-5V, 1-5V, 0-10V | RTD: Pt100, Pt1000, Cu50 | Input: NPN / PNP universal | RS485 half-duplex, transparent transmission |
Thermocouple: K, E, J, T, S | Output: SPDT relay | |||
Measurement Accuracy | ±0.2% F.S. full temperature compensated | Pt100: ±0.2℃ | Input: ±1ms repeatability | ±0.01% signal transmission deviation |
Thermocouple: ±0.5℃ | Output: contact rating accuracy | |||
ADC Resolution | 16-bit high-precision sigma-delta ADC | 24-bit dedicated temperature ADC | — | — |
Sampling Rate | 10Hz per channel, multi-channel sequential sampling | 5Hz per channel | Input: 100Hz scanning | Full baud rate wire-speed forwarding |
Dimension Chart