SPD DIN Rail Signal Surge Protector for Control Cabinets

The SPD DIN Rail Signal Surge Protector provides fast, passive protection for industrial signal loops against lightning and switching transients, with flexible multi-protocol integration for control cabinets.
SKU:
Availability:
Quantity:

SPD DIN Rail Signal Surge Protector

20kA DIN rail surge protector clamping lightning and switching transients before industrial control equipment

Clamp the Surge Before It Reaches Your Control System

SPD is designed to protect industrial instrumentation and control circuits against transient overvoltage caused by lightning and switching events. With a nominal discharge current of 10kA, maximum discharge current of 20kA and response time of ≤1ns, it rapidly diverts surge energy before it reaches sensitive downstream electronics.

industrial signal surge protector for analog temperature and RS485 field signal loops

Protect Different Industrial Signal Loops

SPD is available in different configurations for industrial analog, temperature and communication circuits. Selection options include analog signals, AI/AO signals, RTD/TC temperature signals and RS485, allowing surge protection to be matched to the actual field loop rather than relying on a single fixed configuration.

compact DIN rail signal surge protector for organized multi-loop control cabinet installation

Built for Organized Control Cabinet Protection

Designed for industrial cabinet integration, SPD uses a compact rail-mounted structure that simplifies installation alongside PLC, I/O and other control components. Single- and dual-channel configurations plus 2-, 3- and 4-wire options allow the protection arrangement to be matched to different field-loop requirements while keeping cabinet layouts organized.

Technical Specifications

Maximum Continuous Operating Voltage (Uc):36V DC, compatible with 24V standard industrial instrument loops


Nominal Discharge Current (In, 8/20μs waveform):10kA per line; withstands repeated surge events


Maximum Discharge Current (Imax, 8/20μs waveform):20kA per line; handles extreme lightning surge conditions


Response Time:<1ns; zero action delay for transient lightning and switching surges


Rated Operating Current (IL):500mA per channel; supports full-scale operation of 2-wire transmitters


Leakage Current @ Uc:<1μA; no static power loss, no transmitter zero drift induced


Surge Cycle Endurance:≥20 operations at nominal discharge current with no performance degradation


Protection Topology:Two-stage cascaded design: primary gas discharge tube + rear-end precision clamping circuit


Compatible Loop Types:4-20mA analog, HART protocol, RS485 / Modbus fieldbus, NAMUR sensors and 24V instrument power loops

Dimension Chart

image.png

Wiring Diagram

SPD 浪涌.jpg

微信图片_20260928101913_515_10.jpg
微信图片_20260928101917_516_10.jpg
Previous: 
Next: 
Tel: +86-400-127-7889 / +86-561-3033839
Phone: +86-19715617532
Add: Building 14, University Science and Technology Park, Fenghuangshan Economic Development Zone, Xiangshan District, Huaibei City, Anhui Province

QUICK LINKS

PRODUCT CATEGORY

MORE LINKS

Copyright © 2026 Anhui Qidian Automation Technology Co., Ltd. All Rights Reserved.|Sitemap|Privacy Policy