WS90201 Potentiometer Resistance Signal Transmitter for Industrial Control

A compact isolated resistance/potentiometer transmitter converting 0–10kΩ inputs into standard 4–20mA/0–5V/0–10V outputs for flexible PLC/DCS integration.
Input Signal:
Output Signal :
Channel:
Power Supply:
Please select
SKU:
Availability:
Quantity:

WS90201 Potentiometer Resistance Signal Transmitter

WS90201 resistance signal transmitter with multiple potentiometer input ranges

Wide-range Resistance Signal Input

WS90201 is a resistance signal isolator designed for a wide resistance input range from 0 to 100kΩ. The broad input capability makes it easier to adapt different resistance measurement requirements while keeping the signal interface centralized in one isolation module. It is suitable for industrial resistance measurement, process monitoring and automation systems.

WS90201 converts resistance signals to 4-20mA 0-5V and 0-10V outputs

Flexible Resistance-to-Standard Signal Conversion

WS90201 converts resistance input signals into standard analog outputs including 4–20mA, 0–20mA, 0–5V and 0–10V. This flexible signal conversion makes resistance measurements easier to integrate with PLC, DCS, displays and other industrial monitoring equipment without changing the field measurement principle.

WS90201 isolated resistance signal transmitter for reliable industrial signal conversion

2500V Isolation with Fast Response

WS90201 combines 2500V AC/1min isolation strength with a response time of ≤10ms. The electrical isolation helps separate field measurement signals from the control side, while the fast response supports timely signal transmission. This combination is suitable for industrial automation systems requiring both signal isolation and responsive measurement.

Working Principle Diagram

image.png

Technical Specifications

Built-in Excitation Source:Constant Voltage 2.0V Basic Excitation


Input Impedance:≥100 MΩ


Maximum Output Load Resistance (4–20 mA):≤500 Ω


Voltage Output Load Impedance (0–5 V/0–10 V):≥10 kΩ


Step Response Time (90% Steady-State Output):≤300 ms


Temperature Drift Coefficient (Full Temperature Range):≤100 ppm/°C FS


Independent Linearity Error:±0.1% FS


Overall Accuracy @ 25°C Ambient Temperature:±0.5% FS (Class 0.5)


Field Calibration Method:Factory-set fixed range; no adjustable ranges


Reverse Signal Support (20–4 mA, 0–10 V):Customizable only for special orders


Two-Wire Sensor Power Supply:Built-in reference excitation


Fault Diagnosis Features:Out-of-range saturation output only; no open-circuit detection


Output Channel Specifications:1 input, 1 output / 1 input, 2 outputs / 1 input, 3 outputs / 1 input, 4 outputs (multi-channel analog output)


Standard Transmitter Output:4–20 mA, 0–5 V, 0–10 V reference signals

Dimension Chart
L*W*H : 100mm x 22 .5mm x 114.5mm

image.png

Wiring Diagram

WS90201.jpg
微信图片_20260928101913_515_10.jpg
微信图片_20260928101917_516_10.jpg
Previous: 
Next: 
Tel: +86-400-127-7889 / +86-561-3033839
Phone: +86-19715617532
Add: Building 14, University Science and Technology Park, Fenghuangshan Economic Development Zone, Xiangshan District, Huaibei City, Anhui Province

QUICK LINKS

PRODUCT CATEGORY

MORE LINKS

Copyright © 2026 Anhui Qidian Automation Technology Co., Ltd. All Rights Reserved.|Sitemap|Privacy Policy